Model No. : | XMT-908 |
---|---|
Brand Name : | CJ |
Control Typel : | Digita |
Ningbo, Zhejiang, China
Deskripsi Produk
Ⅰ 、 Spesifikasi Teknis Utama
L pengukuran penyimpangan: ≤ ± 0,5%f · s ± 1
L Kompensasi Kompensasi Akhir Dingin: ≤ ± 2.0 ℃
l Siklus Pengambilan Sampel: 0,5S
l Siklus kontrol: output relai 2 ~ 120S, lainnya adalah 2s.
l relai output kapasitas kontak: AC250V/7A (beban resistansi) atau AC250V/0.3A (beban persepsi)
l Mengemudi output pulsa yang dapat dikendalikan: ≥3V lingkup, ≥40us lebar lebih dari nol atau pemicu pulsa kontak
l Mengemudi output sinyal relai padat: Mengemudi arus listrik ≥15mA, tegangan ≥9v.
l PID kontinu: 0 ~ 10mA (beban 500 ± 200Ω), 4 ~ 20mA (beban 250 ± 100Ω),
atau 0 ~ 5V (beban ≥100kΩ), 1 ~ 5V (beban ≥100kΩ)
l Catu Daya: AC85V ~ 242V, 50/60Hz
L Kondisi Kerja: Suhu 0 ~ 50.0 ℃, Kelembaban Relatif ≤85%RH, Tanpa Korosi dan Radiasi Listrik yang Kuat.
Ⅱ 、 Kode Produk:
Xmt □ 9 □ 8 □
(1) ⑵ (3) (4) (5)
(1) Dimensi Faceplate Meter
Blank: 160mm × 80mm x 120mm Instalasi Lubang: 152mm x 76mm
A: 96mm x 96mm x 110mm Instalasi Lubang: 92mm x 92mm
D: 72mm x 72mm x 110mm Lubang instalasi: 68mm x 68mm
E: 48mm x 96mm x 110mm Lubang Instalasi: 44mm x 92mm
F: 96mm x 48mm x 110mm Instalasi Lubang: 92mm x 44mm
S: 80mm x 160mm x 120mm Lubang Instalasi: 76mm x 156mm
G: 48mm x 48mm x 110mm Instalasi Lubang: 44mm x 44mm
(2) Desain nomor seri
(3) Alarm
“0”: tidak ada alarm “1or2”: satu alarm (batas atas, batas bawah) “5”: alarm suara
"3": dua alarm grup (batas atas, batas bawah, alarm penyimpangan positif dan pengaturan diskresi alarm deviasi negatif)
(4) Sinyal Input
"8": Pertukaran gratis dari sinyal input
⑸ Metode Kontrol
Blank: Kontak relay
"A": penyesuaian pemicu over-nol fase tunggal
"A3": Penyesuaian pemicu over-nol tiga fase
"B": Penyesuaian pemicu fase-fase-fase tunggal
"B3": Penyesuaian pemicu pemicu fase tiga fase
“C”: 0-10mA atau 4-20mA output arus listrik konstan
“G”: Solid State Relay (SSR) Output
Ⅲ 、 Instruksi Panel (Konsultasikan)
Ⅳ 、 mode pengaturan kode
Series |
Code |
Name |
Setting range |
Manual |
Remarks |
0 |
SP |
Appointed data |
Determined by P-SL P-SH |
- |
50.0 |
1 |
AL-1 |
Alarm 1 |
Determined by P-SL,P-SH when the upper and lower limit range,it is0~50.0 when the upper and lower limit deviation alarm |
Alarm 1 setting value |
10 |
2 |
AL-2 |
Alarm 2 |
Determined by P-SL,P-SH when the upper and lower limit range,it is0~50.0 when the upper and lower limit deviation alarm |
Alarm 1 setting value |
10 |
3 |
P |
Proportion modulus |
0~100 |
When the P↑,the the proportion function↓ When P=0,the meter is ON/OFF control |
8 |
4 |
I |
Calculus time |
0~2000S |
240 |
|
5 |
d |
differential time |
0~200S |
30 |
|
6 |
At |
Setting itself |
ON:open setting inself function OFF:close setting itself function |
Select of setting itself |
OFF |
7 |
t |
SSR proportion Control period |
1~120S |
the movements cycle ON/OFF of Setting relays control is no meaning |
20 |
8 |
Hy |
Main control by drop in level |
0.1~50.0 |
Only have meaning when main control output is ON/OFF(P=0) |
1.0 |
9 |
Hy-1 |
Alarm 1 drop in level |
0.1~50.0 |
It has use drop in level setting of alarm contact output |
1.0 |
10 |
Hy-2 |
Alarm 2 drop in level |
0.1~50.0 |
It has use dropin level setting of alarm contact output |
1.0 |
11 |
Pb |
Sensor error amendment |
±20.0 |
The sensor have deviation can use item to revisal |
0 |
12 |
FILT |
Filt modulus |
0~50 |
Is the software filter constants of measurement sampling.The constant ↑,the Measurements antijamming capabilityMeasurements antijamming capability↑,but the measurement and system time ↓ |
20 |
13 |
dp |
Show accuracy |
0~1 |
0: have radix point,1: have no radix point |
- |
14 |
P-SH |
Display the high limit |
P-SL~9999 |
Can set the high limit displaying input signal |
400 |
15 |
P-SL |
Display the low limit |
-1999~P-SH |
Can set the low limit displaying input signal |
0 |
16 |
OUTL |
Allow exports min value |
0~OUTH |
It will no role when highest outputlimit,,manual and position. |
200.0 |
17 |
OUTH |
Allow exports max value |
OUTL~200 |
It will no role when lowest outputlimit,,manual and position. |
0.0 |
18 |
ALP1 |
Alarm1 and output definition |
0~4 |
‘0’:indicate no alarm
‘1’:upper limit touch alarm ‘2’:lower limit touch alarm ‘3’:upper windage alarm ‘4’:lower windage alarm |
- |
19 |
ALP2 |
Alarm2 and output definition |
0~4 |
- |
|
20 |
COOL |
System function choice |
0~1 |
‘0’:reverse control ‘1’:positive control |
0 |
21 |
OPPO |
Open power output |
0~100 |
Soft start functionthat meters coefficient after first export of electric power |
0 |
22 |
LOCK |
Code lock |
0~50 |
0- all the parameter can be revised 1- only the sp can be revised |
0 |
23 |
Sn |
Input type |
0~70. |
0-CU50 (-50.0~150.0℃) ;1-PT1 (-200.0~200.0℃) ;2-PT2 (-200.0~600.0℃) ;3-K (0~1300℃) ;4-E (0~700.0℃) ;5-J (0~900.0℃) ;6-T (-200~400.0℃) ;7-S (0~1600℃) ; | |
24 |
OP-A |
Output type |
1~4 |
1- RLP SSR output mode 2- SSR solid state relay 3- Zero controllable silicon contact signal when it exceed zero output mode 4- Mut controllable silicon phase trigger contact output mode 5- 0~10MA linearity control electric current output 6- 4~20MA linearity control electric current output |
Ⅴ 、 indeks teknis
1 、 Area pengaturan pertama
Tekan tombol Set 3S masuk ke area pengaturan pertama, meter akan menampilkan kode parameter 1 ~ 24 di jendela di baris atas dan menampilkan data parameter di baris rendah. Pada saat ini tekan tombol ▲ 、 ▼ atau T untuk menyesuaikan parameter, lalu tekan tombol Set untuk melestarikan. Tekan tombol Set lama akan menarik atau tekan tombol + ƒ akan langsung menarik. Jika dalam 10 detik tidak menekan setiap tombol maka secara otomatis akan melestarikan data dan menarik pengaturan.
2 、 Area pengaturan kedua
Ketika meter diatur dengan listrik, tekan tombol set masuk ke area pengaturan kedua, Anda dapat sesuai 1 untuk mengatur "SP".
3 、 Peraturan Manual
Ketika meter diatur dengan listrik, tekan tombol T sekitar 3s masuk ke dalam regulasi manual, itu akan menampilkan "h" di baris bawah, pada saat ini dapat mengatur daya output; Tekan tombol T sekitar 3s lagi itu akan menarik peraturan manual.
Ⅵ 、 pengaturan itu sendiri
Penggunaan meter pada pertama kalinya atau sekitarnya memiliki pengubah, menemukan itu mengendalikan tidak baik, saat ini Anda perlu menggunakan pengaturan itu sendiri. Misalnya:
Set pertama AT = ON, AM Light berkedip, meter masuk ke pengaturan itu sendiri, tekan tombol Set Enter ke dalam pengaturan parameter. Atur HY adalah 0,5 ~ 1 ℃, jika output adalah Relai mengatur t = 2s, meter memiliki tiga kali bergetar, parameter P, I, D yang diawetkan secara otomatis, dan AT Light Off, pengaturan itu sendiri selesai.